Data Center Design by ARISTOS INTERNATIONAL, INC.

The level (Tier) of data center required for your business will vary widely depending on requirements for redundancy and concurrent maintainability.

Levels of Data Center Reliability...

The Uptime Institute categorizes businesses into four tiers:

Tier 1: Small businesses where IT enhances internal business processes.

Tier 2: Companies that do not depend on real-time or online delivery of goods and services, where systems can be shut down during off hours.

Tier 3: Companies that support internal and external clients 24 x 7 (help desks); businesses that span multiple locations; businesses where IT supports automated business processes.

Tier 4: Businesses based on e-commerce or online transactions - any business that runs 24 x 7, is client-facing and international in scope; large global operations where access must be 24 x 7 to accommodate different time zones

...Determine Facility Infrastructure Needs and Costs

  Tier I Tier II Tier III Tier IV
Number of delivery paths Only 1 Only 1 1 Active/1 Passive 2 Active
Redundant components N N+1 N+1 2(N+1) or S + S
Support space to raised floor ratio 20% 30% 80-90% 100%
Initial watts/SF 20-30 40-50 40-60 50-80
Ultimate watts/SF 20-30 40-50 100-150 150+
Raised floor height 12 inches 18 inches 30-36 inches 30-36 inches
Floor loading pounds/SF 85 100 150 150+
Utility voltage 208, 480 208, 480 12-15kV 12-15kV
Months to implement 3 3 to 6 15 to 20 15 to 20
Year first deployed 1965 1970 1985 1995
Annual IT downtime due to site 28.8 hours 22.0 hours 1.6 hours 0.4 hours
Site availability 99.671% 99.749% 99.982% 99.995%
Source: The uptime institute